Fire Resistance of cold room panel is the core factor for cold storage construction safety and cold room use safety. Every year cold storage fire disasters happen a lot around the world, and cause huge losses of properties and human lives.
Two main factors cause the dangers of cold storage fire : First, the spread of flammability of many cold room panels enlarge rapid fire expansion. Second, the burning fire droplets ignite other combustible things on the floor.
To tackle these two main fire factors, our PIR and PUR Cold Storage Boards have the features of :
Inspection Item | Measurement & Unit | Technical Requirements B1(C) Level |
Inspection Data | Single-Item Evaluation |
---|---|---|---|---|
Fire Growth Rate (Combustion Performance) |
FIGRA0.4MJ (W/s) | ≦250 | 130 | PASS |
Lateral Flame Spread (Combustion Performance) |
LFS (m) | The lateral flame spread does not reach the long wing edge of the test sample | The lateral flame spread does not reach the long wing edge of the test sample | PASS |
Total Heat Release (Combustion Performance) |
THR600s (M/J) | ≦15 | 5 | PASS |
Flammability | mm | Combustible flame tip height Fs ≦ 150mm in 60s | 58 | PASS |
/ | No phenomenon of burning droplets igniting filter paper in 60s | No burning droplets | PASS | |
Oxygen Index | OI (%) | ≧30 | 33.5 | PASS |
Inspection Basis:
Inspection Items: Fire Growth Rate, Lateral Flame Spread, Total Heat Release, Flammability, and Oxygen Index.
Inspection Conclusion: After inspection, the tested items meet the requirements of above listed standards. The test data can be found in the above inspection results (attached table).
Our aim is not only provide Safe Cold Room Panels, but also supply High Insulation Efficiency Cold Storage Boards to our cold storage customers in different industries. Know more about PIR and PUR Cold Room Panels: